PRO-RK10KVA
Ean : 8054608901391
Gruppo di Continuità Rack Pro Power UPS 10000 VA
* Non viene rilasciata alcuna garanzia su eventuali errori delle descrizioni tecniche aggiuntive né sull'accuratezza delle foto, da intendersi come un mero servizio informativo
Documento senza titolo
Model |
PRO-RK10KVA |
INPUT |
Phase |
Single Phase |
Voltage Range |
110-280VAC |
Frequency Range |
45~70Hz |
Current Distortion |
<3% |
Power Factor |
Up to 0.99 @ 100% linear mode |
OUTPUT |
Voltage (without transformer) |
220/208/220/230/240 Vac, settable |
Capacity |
10000VA/10000W |
Power Factor |
1 |
Voltage Distortion |
=2% @100% load |
=7% @100% non-linear load |
Output Voltage Regulation |
without transformer |
±1% |
with transformer |
±3% |
Frequency Range |
±1Hz or ±3Hz (Selectable) |
Crest Factor |
3:1 |
Output Waveform |
Pure Sinewave |
EFFICIENCY |
Online Mode |
Up to 94% |
ECO Mode |
Up to 98% |
PHYSICAL |
Dimensions (WxHxD, mm) |
440x132x685 |
Net Weight (kg) |
21.5 |
BATTERY |
Number |
16/18/20 |
Type |
VRLA, Sealed maintenance free lead acid |
Recharge Time (to 90%) |
4 hours |
Charger (16/18/20 model) |
2-step (CC-CV), 1.7A (max.) |
Internal batteries |
-- |
Battery |
Code |
C20X3U00 |
Bank |
Max quantities |
20 |
Dimension (WxHxD, mm) |
440x132x685 |
DISPLAY |
Status on LED + LCD |
Line mode, backup mode, ECO mode, bypass supply, battery low, battery bad/disconnect, overload UPS fault |
Readings on LCD |
Input voltage, input frequency, output voltage, output current, output frequency, load percentage, battery voltage, inner temperature, backup time estimation |
Self-Diagnostics |
Upon power-on, manual control by panel & communication, self routine check |
ALARM |
Audible or Visual |
Line failure/Battery low/Transfer to bypass/System fault |
PROTECTION |
Full Protection |
Overload, Over temperature, short circuit, overcharge |
FUNCTION |
Multi-Mode |
Normal/ECO/Frequency converter |
DC start |
Yes |
Parallel capacity |
Up to 4 units |
Parallel redundancy |
3+1 |
ENVIRONMENT |
Operation Temperature |
0~40°C |
Operation Humidity |
0%~90% (without condensing) |
Altitude |
1000m without derating |
Noise Level |
=60dBA @ 1 meter |
INTERFACE |
Standard |
USB, EPO/ROO |
Option |
RS232, RS485, Dry contact card, SNMP/WEB card, 2nd RS232 card |
Compatible platforms |
Microsoft Windows series, Linux, Mac |
STANDARDS & CERTIFICATIONS |
Safety & EMC |
IEC EN 62040-1, IEC EN 62040-2 |
Performance |
IEC EN 62040-3 |
Marks |
CE |
|